Show Filters
Part B Fire Safety

Section 16: Venting of heat and smoke from basements – flats

Share

Section 16: Venting of heat and smoke from basements – flats

Provision of smoke outlets

16.1 Heat and smoke from basement fires vented via stairs can inhibit access for firefighting personnel.
This may be reduced by providing smoke outlets, or smoke vents, which allow heat and smoke to escape from the basement levels to the open air. They can also be used by the fire and rescue service to let cooler air into the basements (Diagram 16.1).

16.2 Each basement space should have one or more smoke outlets.
Where this is not practicable (for example, the plan area is deep and the amount of external wall is restricted by adjoining buildings), the perimeter basement spaces may be vented, with other spaces vented indirectly by opening connecting doors. This does not apply for places of special fire hazard (see paragraph 16.7).

If a basement is compartmented, each compartment should have one or more smoke outlets, rather than indirect venting.

A basement storey or compartment containing rooms with doors or windows does not need smoke outlets.

16.3 Smoke outlets connecting directly to the open air should be provided from every basement storey, except for any basement storey that has both of the following.

a. A maximum floor area of 200m2.

b. A floor a maximum of 3m below the adjacent ground level.

16.4 Strong rooms do not need to be provided with smoke outlets.

Natural smoke outlets

16.5 Smoke outlets should be both of the following.

a. Sited at high level in either the ceiling or wall of the space they serve.

b. Evenly distributed around the perimeter, to discharge to the open air.

16.6 The combined clear cross-sectional area of all smoke outlets should be a minimum of 1/40 of the area of the floor of the storey they serve.

16.7 Separate outlets should be provided from places of special fire hazard.

16.8 If the smoke outlet terminates at a point that is not readily accessible, it should be kept unobstructed and covered only with a class A1 grille or louvre.

16.9 If the smoke outlet terminates in a readily accessible position, it may be covered by a panel, stallboard or pavement light that can be broken out or opened. The position of covered smoke outlets should be suitably indicated.

16.10 Outlets should not be placed where they prevent the use of escape routes from the building.

Mechanical smoke extract

16.11 If basement storeys are fitted with a sprinkler system in accordance with Appendix E, a mechanical smoke extraction system may be provided as an alternative to natural venting. Sprinklers do not need to be installed on the other storeys unless needed for other reasons.

Car parks are not normally expected to be fitted with sprinklers (see Section 11 of Approved Document B Volume 2).

16.12 The air extraction system should comply with all of the following.

a. It should give at least 10 air changes per hour.

b. It should be capable of handling gas temperatures of 300°C for not less than one hour.

c. It should do either of the following.

i. Be activated automatically if the sprinkler system activates.

ii. Be activated by an automatic fire detection system that conforms to BS 5839-1 (minimum L3 standard).

Further information on equipment for removing hot smoke is given in BS EN 12101-3.

general G6

Diagram 16.1 Fire resisting construction for smoke outlet shafts

Construction of outlet ducts or shafts

16.13 Outlet ducts or shafts, including any bulkheads over them (see Diagram 16.1), should be enclosed in construction of class A1 rating and fire resistance at least equal to that of the element through which they pass.

16.14 Natural smoke outlet shafts should be separated from each other using construction of class A1 rating and fire resistance at least equal to that of the storeys they serve, where the shafts are either of the following.

a. From different compartments of the same basement storey.

b. From different basement storeys.

Regulation 38: Fire safety information
This section deals with the following regulation of the Building Regulations 2010.

Fire safety information

38. (1) This regulation applies where building work—

(a) consists of or includes the erection or extension of a relevant building; or

(b) is carried out in connection with a relevant change of use of a building,
and Part B of Schedule 1 imposes a requirement in relation to the work.

(2) The person carrying out the work shall give fire safety information to the responsible person not later than the date of completion of the work, or the date of occupation of the building or extension, whichever is the earlier.

(3) In this regulation—

(a) “fire safety information” means information relating to the design and construction of the building or extension, and the services, fittings and equipment provided in or in connection with the building or extension which will assist the responsible person to operate and maintain the building or extension with reasonable safety;

(b) a “relevant building” is a building to which the Regulatory Reform (Fire Safety) Order 2005 applies, or will apply after the completion of building work;

(c) a “relevant change of use” is a material change of use where, after the change of use takes place, the Regulatory Reform (Fire Safety) Order 2005 will apply, or continue to apply, to the building; and

(d) “responsible person” has the meaning given by article 3 of the Regulatory Reform (Fire Safety) Order 2005.

Intention

The aim of this regulation is to ensure that the person responsible for the building has sufficient information relating to fire safety to enable them to manage the building effectively. The aim of regulation 38 will be achieved when the person responsible for the building has all the information to enable them to do all of the following.

a. Understand and implement the fire safety strategy of the building.

b. Maintain any fire safety system provided in the building.

c. Carry out an effective fire risk assessment of the building.

External works Fire safety Heat pumps External insulation Cavity wall insulation Wall ties Air to water heat pump Air to air heat pump Air to ground heat pump Gas boiler IS 440 Ceiling insulation Suspended floor Stairs Time and temperature Percoltion area Ground conditions Two storey Three storey Air tightness Air tightness tape Fire stopping Fire mastic Fire wraps Fire board Tongue and groove Building energy rating Retrofit assessment Home energy assessment External wall insulation Windows External doors Fire doors Internal doors Wall tiles Floor tiles Mechanical ventilation Natural ventilation Trickle vents Air tight membrane Fire cable Sash windows Light gauge steel