Section 5: Internal fire spread – dwellinghouses

Share

Section 5: Internal fire spread – dwellinghouses

Loadbearing elements of structure

Fire resistance standard

5.1 Elements such as structural frames, beams, columns, loadbearing walls (internal and external), floor structures and gallery structures should have, as a minimum, the fire resistance given in Appendix B, Table B3.

5.2 If one element of structure supports or stabilises another, as a minimum the supporting element should have the same fire resistance as the other element.

5.3 The following are excluded from the definition of ‘element of structure’.

a. A structure that supports only a roof, unless either of the following applies.

i. The roof performs the function of a floor, such as a roof terrace, or as a means of escape.

ii. The structure is essential for the stability of an external wall that needs to be fire resisting (e.g. to achieve compartmentation or for the purposes of preventing fire spread between buildings).

b. The lowest floor of the building.

c. External walls, such as curtain walls or other forms of cladding, which transmit only self weight and wind loads and do not transmit floor load.

NOTE: In some cases, structural members within a roof may be essential for the structural stability system of the building. In these cases, the structural members in the roof do not just support a roof and must demonstrate the relevant fire resistance for the building as required by paragraph 5.2 above.

Floors in loft conversions

5.4 Where adding an additional storey to a two storey single family dwellinghouse, new floors should have a minimum REI 30 fire resistance. Any floor forming part of the enclosure to the circulation space between the loft conversion and the final exit should achieve a minimum rating of REI 30.

The existing first-storey construction should have a minimum rating of R 30. The fire performance may be reduced for integrity and insulation, when both of the following conditions are met.

a. Only one storey is added, containing a maximum of two habitable rooms.

b. The new storey has a maximum total area of 50m2.

Compartmentation

Provision of compartmentation

5.5 Dwellinghouses that are semi-detached or in terraces should be considered as separate buildings. Every wall separating the dwellinghouses should be constructed as a compartment wall (see paragraphs 5.8 to 5.12).

5.6 If a garage is attached to or forms an integral part of a dwellinghouse, the garage should be separated from the rest of the dwellinghouse by fire resisting construction (minimum REI 30) (Diagram 5.1).

5.7 Where a door is provided between a dwellinghouse and the garage (see Diagram 5.1), it should meet one of the following conditions.

a. The garage floor should be laid such that it falls away from the door to the outside, to allow fuel spills to flow away.

b. The door opening should be a minimum of 100mm above the level of the garage floor.

general G6
Diagram 5.1 Separation between garage and dwellinghouse

Construction of compartment walls and compartment floors

General provisions

5.8 All compartment walls and compartment floors should achieve both of the following.

a. Form a complete barrier to fire between the compartments they separate.

b. Have the appropriate fire resistance, as given in Appendix B, Table B3 and Table B4.

5.9 Timber beams, joists, purlins and rafters may be built into or carried through a masonry or concrete compartment wall if the openings for them are both of the following.

a. As small as practicable.

b. Fire-stopped.

If trussed rafters bridge the wall, failure of the truss due to a fire in one compartment should not cause failure of the truss in another compartment.

Compartment walls between buildings

5.10 Adjoining buildings should only be separated by walls, not floors. Compartment walls common to two or more buildings should comply with both of the following.

a. Run the full height of the building in a continuous vertical plane.

b. Be continued through any roof space to the underside of the roof (see Diagram 5.2).

Junction of compartment wall with roof

5.11 A compartment wall should achieve both of the following.

a. Meet the underside of the roof covering or deck, with fire-stopping to maintain the continuity of fire resistance.

b. Be continued across any eaves.

5.12 To reduce the risk of fire spreading over the roof from one compartment to another, a 1500mm wide zone of the roof, either side of the wall, should have a covering classified as BROOF(t4), on a substrate or deck of a material rated class A2-s3, d2 or better, as set out in Diagram 5.2a.

Thermoplastic rooflights that, because of paragraph 12.7, are regarded as having a BROOF(t4) classification are not suitable for use in that zone.

5.13 Materials achieving class B-s3, d2 or worse used as a substrate to the roof covering and any timber tiling battens, fully bedded in mortar or other suitable material for the width of the wall (Diagram 5.2b), may extend over the compartment wall in buildings that are a maximum of 15m high.

5.14 Double-skinned insulated roof sheeting should incorporate a band of material rated class A2-s3, d2 or better, a minimum of 300mm in width, centred over the wall.

5.15 As an alternative to the provisions of paragraphs 5.12 to 5.14, the compartment wall may extend through the roof for a minimum of either of the following (see Diagram 5.2).

a. Where the height difference between the two roofs is less than 375mm, 375mm above the top surface of the adjoining roof covering.

b. 200mm above the top surface of the adjoining roof covering where either of the following applies.

i. The height difference between the two roofs is 375mm or more.

ii. The roof coverings either side of the wall are of a material classified as BROOF(t4).

general G6
Diagram 5.2 Junction of compartment wall with roof

Cavities

5.16 Cavities in the construction of a building provide a ready route for the spread of smoke and flame, which can present a greater danger as any spread is concealed. For the purpose of this document, a cavity is considered to be any concealed space.

5.17 To reduce the potential for fire spread, cavity barriers should be provided for both of the following.

a. To divide cavities.

b. To close the edges of cavities.

Cavity barriers should not be confused with fire-stopping details (Section 9).

5.18 Cavity barriers should be provided at all of the following locations.

a. At the edges of cavities, including around openings (such as windows, doors and exit/entry points for services).

b. At the junction between an external cavity wall and every compartment floor and compartment wall.

c. At the junction between an internal cavity wall and every compartment floor, compartment wall or other wall or door assembly forming a fire resisting barrier.

This does not apply where a wall meets the conditions of Diagram 5.3.

5.19 It is not appropriate to complete a line of compartment walls by fitting cavity barriers above them. The compartment wall should be extended to the underside of the floor or roof above.

general G6
Diagram 5.3 Cavity walls excluded from provisions for cavity barriers

Construction and fixings for cavity barriers

5.20 Cavity barriers, tested from each side separately, should provide a minimum of both of the following:

a. 30 minutes’ integrity (E 30)

b. 15 minutes’ insulation (I 15).

They may be formed by a construction provided for another purpose if it achieves the same performance.

5.21 Cavity barriers in a stud wall or partition, or provided around openings, may be formed of any of the following.

a. Steel, a minimum of 0.5mm thick.

b. Timber, a minimum of 38mm thick.

c. Polythene-sleeved mineral wool, or mineral wool slab, under compression when installed in the cavity.

d. Calcium silicate, cement-based or gypsum-based boards, a minimum of 12mm thick. These do not necessarily achieve the performance specified in paragraph 5.20.

NOTE: Cavity barriers provided around openings may be formed by the window or door frame, if the frame is constructed of steel or timber of the minimum thickness in (a) or (b), as appropriate.

5.22 Cavity barriers should be tightly fitted to a rigid construction and mechanically fixed in position. If this is not possible (e.g. where a cavity barrier joins to slates, tiles, corrugated sheeting or similar materials) the junction should be fire-stopped.

5.23 Cavity barriers should be fixed so their performance is unlikely to be made ineffective by any of the following.

a. Movement of the building due to subsidence, shrinkage or temperature change, and movement of the external envelope due to wind.

b. During a fire, collapse of services penetrating the cavity barriers, either by the failure of the supporting system or through degradation of the service itself (e.g. by melting or burning).

c. During a fire, failure of the cavity barrier fixings. (In roof spaces, where cavity barriers are fixed to roof members, there is no expectation of fire resistance from roof members provided for the purpose of support.)

d. During a fire, failure of any material or construction to which cavity barriers abut. (For example, a suspended ceiling that continues over a fire resisting wall or partition collapses, and the cavity barrier fails prematurely because the ceiling was not designed to provide a minimum fire resistance of EI 30.)

Openings in cavity barriers

5.24 Openings should be limited to the following.

a. Fire doorsets with a minimum E 30 rating, fitted in accordance with Appendix C.

b. The passage of pipes that follow the provisions in Section 9.

c. The passage of cables or conduits containing one or more cables.

d. Openings fitted with a suitably mounted and appropriate fire damper.

e. Ducts that are either of the following.

i. Fire resisting (minimum E 30).

ii. Fitted with a suitably mounted and appropriate fire damper where they pass through the cavity barrier.

NOTE: For further guidance on openings in cavity barriers see Section 9.

First fix External works Fire safety Roof Cavity Floors External insulation Cavity wall insulation Underfloor insulation Wall ties Radon barrier Underfloor heating pipes Air to water heat pump Air to air heat pump Air to ground heat pump Insulated concrete formwork Timber frame IS 440 Structurally insulated panels Ceiling insulation Roof insulation Mineral wool Joists Suspended floor Intermediate floors Conversion Time and temperature Zone control Percoltion area Two storey Ground conditions Three storey Detached Semi detached Fire stopping Fire mastic Fire wraps Fire board Sound insulation Tiling Tongue and groove Building energy rating Energy performance certificate Bead insulation Pumped insulation Pump cavity External wall insulation Windows Roof lights External doors Fire doors Internal doors Tiles Wall tiles Floor tiles Eaves box Cables Fire cable Sash windows Light gauge steel