Show Filters
Part B Fire Safety

Section 9: Protection of openings and fire stopping

Share

Section 9: Protection of openings and fire stopping

Introduction

9.1 The performance of a fire-separating element should not be impaired. Every joint, imperfect fit and opening for services should be sealed. Fire-stopping delays the spread of fire and, generally, the spread of smoke as well.

Openings for pipes

9.2 Pipes passing through a fire-separating element, unless in a protected shaft, should meet one of the alternatives A, B or C below.

Alternative A: Proprietary seals (any pipe diameter)

9.3 Provide a proprietary, tested sealing system that will maintain the fire resistance of the wall, floor or cavity barrier.

Alternative B: Pipes with a restricted diameter

9.4 Where a proprietary sealing system is not used, fire-stop around the pipe, keeping the opening for the pipe as small as possible. The nominal internal diameter of the pipe should not exceed the relevant dimension given in Table 9.1. The diameter given in Table 9.1 for pipes of specification (b) used in situation 2 or 3 assumes that the pipes are part of an above-ground drainage system and are enclosed as shown in Diagram 9.1. If they are not, the smaller diameter given for situation 5 should be used.

Alternative C: Sleeving

9.5 A pipe with a maximum nominal internal diameter of 160mm may be used with a sleeve made out of a high melting point metal, as shown in Diagram 9.2, if the pipe is made of one of the following.

a. Lead.

b. Aluminium.

c. Aluminium alloy.

d. Fibre-cement.

e. uPVC (pipes should also comply with either BS 4514 or BS 5255).

A high melting point metal means any metal (such as cast iron, copper or steel) which, if exposed to a temperature of 800°C, will not soften or fracture to the extent that flame or hot gas will pass through the wall of the pipe.

general G6
Diagram 9.1 Enclosure for drainage or water supply pipes

general G6
Diagram 9.2 Pipes penetrating structure

general G6
Table 9.1 Maximum nominal internal diameter of pipes passing through a compartment wall/floor

Mechanical ventilation and air conditioning systems

General provisions

9.6 Ductwork should not help to transfer fire and smoke through the building. Terminals of exhaust points should be sited away from final exits, cladding or roofing materials achieving class B-s3, d2 or worse and openings into the building.

9.7 Ventilation ducts supplying or extracting air directly to or from a protected stairway should not also serve other areas. A separate ventilation system should be provided for each protected stairway.

9.8 A fire and smoke damper should be provided where ductwork enters or leaves each section of the protected escape route it serves. It should be operated by a smoke detector or suitable fire detection system. Fire and smoke dampers should close when smoke is detected. Alternatively, the methods set out in paragraphs 9.16 and 9.17 and Diagrams 9.3 and 9.4 may be followed.

9.9 In a system that recirculates air, smoke detectors should be fitted in the extract ductwork before both of the following.

a. The point where recirculated air is separated from air to be discharged to the outside.

b. Any filters or other air cleaning equipment.
When smoke is detected, detectors should do one of the following.

i. Cause the system to immediately shut down.

ii. Switch the ventilation system from recirculating mode to extraction to divert smoke to outside the building.

9.10 In mixed use buildings, non-domestic kitchens, car parks and plant rooms should have separate and independent extraction systems. Extracted air should not be recirculated.

9.11 Under fire conditions, ventilation and air-conditioning systems should be compatible with smoke control systems and need to be considered in their respective design.

Ventilation ducts and flues passing through fire separating elements

General provisions

9.12 If air handling ducts pass through fire-separating elements, the load-bearing capacity, integrity and insulation of the elements should be maintained using one or more of the following four methods. In most ductwork systems, a combination of the four methods is best to combat potential fire dangers.

a. Method 1 – thermally activated fire dampers.

b. Method 2 – fire resisting enclosures.

c. Method 3 – protection using fire resisting ductwork.

d. Method 4 – automatically activated fire and smoke dampers triggered by smoke detectors.

9.13 Further information on fire resisting ductwork is given in the ASFP Blue Book.

Flats and dwellings

9.14 Where ducts pass between fire-separating elements to serve multiple flats or dwellings, fire dampers or fire and smoke dampers should be actuated by both of the following.

a. Smoke detector-controlled automatic release mechanisms.

b. Thermally actuated devices.

Kitchen extract

9.15 Methods 1 and 4 should not be used for extract ductwork serving kitchens. The likely build-up of grease within the duct can adversely affect dampers.

Ducts passing through protected escape routes

9.16 Method 1 should not be used for extract ductwork passing through the enclosures of protected escape routes (Diagrams 9.3 and 9.4), as large volumes of smoke can pass thermal devices without triggering them.

9.17 An ES classified fire and smoke damper which is activated by a suitable fire detection system (method 4) may also be used for protected escape routes.

general G6
Diagrams 9.3 Ductwork passing through protected escape routes - method 2 or method 3

general G6
Diagrams 9.4 Ductwork passing through protected escape routes - method 4

Installation and specification of fire dampers

9.18 Both fire dampers and fire and smoke dampers should be all of the following.

a. Sited within the thickness of the fire-separating elements.

b. Securely fixed.

c. Sited such that, in a fire, expansion of the ductwork would not push the fire damper through the structure.

9.19 Access to the fire damper and its actuating mechanism should be provided for inspection, testing and maintenance.

9.20 Fire dampers should meet both of the following conditions.

a. Conform to BS EN 15650.

b. Have a minimum E classification of 60 minutes or to match the integrity rating of the fire resisting elements, whichever is higher.

9.21 Fire and smoke dampers should meet both of the following conditions.

a. Conform to BS EN 15650.

b. Have a minimum ES classification of 60 minutes or to match the integrity rating of the fire resisting elements, whichever is higher.

9.22 Smoke detectors should be sited so as to prevent the spread of smoke as early as practicable by activating the fire and smoke dampers. Smoke detectors and automatic release mechanisms used to activate fire dampers and/or fire and smoke dampers should conform to BS EN 54-7 and BS 5839-3 respectively.

Further information on fire dampers and/or fire and smoke dampers is given in the ASFP Grey Book.

Flues, etc.

9.23 The wall of a flue, duct containing flues or appliance ventilation duct(s) should have a fire resistance (REI) that is at least half of any compartment wall or compartment floor it passes through or is built into (Diagram 9.5).

general G6
Diagram 9.5 Flues penetrating compartment walls or floors

Fire stopping

9.24 In addition to any other provisions in this section, both of the following conditions should be met.

a. Joints between fire-separating elements should be fire-stopped.

b. Openings through a fire resisting element for pipes, ducts, conduits or cable should be all of the following.

i. As few as possible.

ii. As small as practicable.

iii. Fire-stopped (allowing thermal movement in the case of a pipe or duct).

NOTE: The fire-stopping around fire dampers, fire resisting ducts, fire and smoke dampers and smoke control ducts should be in accordance with the manufacturer or supplier’s installation instructions.

9.25 Materials used for fire-stopping should be reinforced with (or supported by) materials rated class A2-s3, d2 or better to prevent displacement in both of the following cases.

a. Where the unsupported span is greater than 100mm.

b. Where non-rigid materials are used (unless subjected to appropriate fire resistance testing to show their suitability).

9.26 Proprietary, tested fire-stopping and sealing systems are available and may be used. Different materials suit different situations and not all are suitable in every situation.

9.27 Other fire-stopping materials include the following.

a. Cement mortar.

b. Gypsum-based plaster.

c. Cement-based or gypsum-based vermiculite/perlite mixes.

d. Glass fibre, crushed rock, blast furnace slag or ceramic-based products (with or without resin binders).

e. Intumescent mastics.

These may be used in situations appropriate to the particular material. Not all materials will be suitable in every situation.

9.28 Guidance on the design, installation and maintenance of measures to contain fires or slow their spread is given in Ensuring Best Practice for Passive Fire Protection in Buildings produced by the Association for Specialist Fire Protection (ASFP).

9.29 Further information on generic systems, their suitability for different applications and guidance on test methods, is given in the ASFP Red Book.

Requirement B4: External fire spread

These sections deal with the following requirement from Part B of Schedule 1 to the Building Regulations 2010. Section 10 also refers to regulation 7(2) of the Building Regulations 2010.
Guidance on regulation 7(1) can be found in Approved Document 7.

Requirement

Requirement

External fire spread

B4. (1) The external walls of the building shall adequately resist the spread of fire over the walls and from one building to another, having regard to the height, use and position of the building.

(2) The roof of the building shall adequately resist the spread of fire over the roof and from one building to another, having regard to the use and position of the building.

Limits on application

Regulation

Regulation 7 – Materials and workmanship

(1) Building work shall be carried out—

(a) with adequate and proper materials which—

(i) are appropriate for the circumstances in which they are used,

(ii) are adequately mixed or prepared, and

(iii) are applied, used or fixed so as adequately to perform the functions for which they are designed; and

(b) in a workmanlike manner.

(2) Subject to paragraph (3), building work shall be carried out so that materials which become part of an external wall, or specified attachment, of a relevant building are of European Classification A2-s1, d0 or A1, classified in accordance with BS EN 13501-1:2007+A1:2009 entitled “Fire classification of construction products and building elements. Classification using test data from reaction to fire tests” (ISBN 978 0 580 59861 6) published by the British Standards Institution on 30th March 2007 and amended in November 2009.

(3) Paragraph (2) does not apply to—

(a) cavity trays when used between two leaves of masonry;

(b) any part of a roof (other than any part of a roof which falls within paragraph (iv) of regulation 2(6)) if that part is connected to an external wall;

(c) door frames and doors;

(d) electrical installations;

(e) insulation and water proofing materials used below ground level;

(f) intumescent and fire stopping materials where the inclusion of the materials is necessary to meet the requirements of Part B of Schedule 1;

(g) membranes;

(h) seals, gaskets, fixings, sealants and backer rods;

(i) thermal break materials where the inclusion of the materials is necessary to meet the thermal bridging requirements of Part L o
(ii) f Schedule 1; or

(j) window frames and glass.

(4) In this regulation—

(a) a “relevant building” means a building with a storey (not including roof-top plant areas or any storey consisting exclusively of plant rooms) at least 18 metres above ground level and which—

(i) contains one or more dwellings;

(ii) contains an institution; or

(iii) contains a room for residential purposes (excluding any room in a hostel, hotel or boarding house); and

(b) “above ground level” in relation to a storey means above ground level when measured from the lowest ground level adjoining the outside of a building to the top of the floor surface of the storey.

Intention

Resisting fire spread over external walls

The external envelope of a building should not contribute to undue fire spread from one part of a building to another part. This intention can be met by constructing external walls so that both of the following are satisfied.

a. The risk of ignition by an external source to the outside surface of the building and spread of fire over the outside surface is restricted.

b. The materials used to construct external walls, and attachments to them, and how they are assembled do not contribute to the rate of fire spread up the outside of the building.

The extent to which this is necessary depends on the height and use of the building.

Resisting fire spread from one building to another

The external envelope of a building should not provide a medium for undue fire spread to adjacent buildings or be readily ignited by fires in adjacent buildings. This intention can be met by constructing external walls so that all of the following are satisfied.

a. The risk of ignition by an external source to the outside surface of the building is restricted.

b. The amount of thermal radiation that falls on a neighbouring building from window openings and other unprotected areas in the building on fire is not enough to start a fire in the other building.

c. Flame spread over the roof and/or fire penetration from external sources through the roof is restricted.

The extent to which this is necessary depends on the use of the building and its position in relation to adjacent buildings and therefore the site boundary.

External works Fire safety Ventilation Roof Cavity Floors External insulation Cavity wall insulation Underfloor insulation Wall ties Radon barrier Underfloor heating pipes Air to water heat pump Air to air heat pump Air to ground heat pump Gas boiler Modular build IS 440 Ceiling insulation Roof insulation Suspended floor Intermediate floors Copper Time and temperature Zone control Drainage Ground conditions Two storey Three storey Air tightness Air tightness tape Fire stopping Fire mastic Fire wraps Fire board Sound insulation Tongue and groove Building energy rating Energy performance certificate Water pump Water tank Bead insulation Pumped insulation Pump cavity External wall insulation Roof lights External doors Fire doors Internal doors Wall tiles Floor tiles Ventilation Mechanical ventilation Natural ventilation Air tight membrane Water membrane Water vapour membrane Vapour control layer Fire cable Light gauge steel